INTRODUCTION
Liquid refrigerant pumping technology has given refrigeration systems capacity boosts
while at the same time saving electrical energy. |
 |
Liquid refrigerant entering the
liquid line is pressurized with a small centrifugal pump shown in Fig. 1, by an amount
equivalent to the pressure loss between the condenser outlet and the thermostatic
expansion valve inlet on receiverless systems, or the receiver and the TEV inlet on
TEV/receiver systems. The liquid becomes subcooled and will not flash if exposed to
pressure drops in the liquid line. |
Figure 1
Liquid centrifugal pump used in the liquid refrigerant pumping system.
| The system is shown in Fig. 2
along with a normal system Fig. 3. Thus, by increasing the pressure of the liquid
refrigerant, the associated saturation temperature is raised because of the pressure
increase, while the actual liquid temperature remains the same. |
 |
Because the centrifugal pump's
motor is external to the refrigeration system, and the impeller is driven by revolving
magnetic field, negligible energy and heat is added to the system.The liquid is
pressurized with negligible addition of temperature or heat, and allows for a completely
sealed system because no drive shaft protrudes through the pump case. The centrifugal pump
can increase the pressure of the liquid by approximately 55.15kPa to 137.8kPa (8 to 20)
psi. |
| LIQUID REFRIGERANT PUMPING SYSTEM |
 |
Since subcooling exists in any
liquid below its saturation temperature for a given pressure, there are really several
ways to subcool liquid. One way is to sensible cool the liquid in the bottom of the
condenser to give it a sensible heat reduction to prevent flashing from liquid line
pressure drops.However, subcooling this way will take up valuable condenser volume with
subcooled liquid at its bottom, since condensing cannot occur in this area. This will
cause higher head pressures and compression ratios, thus lower efficiencies. |
| If we consider only the subcooling
of the liquid without regards to decreasing condenser surface area, we will see a gain of
1/2% of capacity for every degree of liquid subcooling**. However, if we consider the
reduction of condenser surface area due to the liquid subcooling, there is a net loss in
capacity due to increased condensing pressures and temperatures. |
This type of subcooling, often called
ambient subcooling, has been practiced for years and was thought to be a free method of
subcooling. This simply is not the case. Ambient subcooling is usually accomplished at the
cost of increased head pressures. It was used in refrigeration systems simply as a liquid
seal in the condenser's bottom, and to prevent liquid line flash gas. This will keep a
solid column of liquid supplied to the metering device.
Also, ambient subcooling cannot be maintained at a given
level with only air side controls. Condensing pressures are directed related to the
temperature of the condenser cooling medium and the useful condensing area in the
condenser. Equation 1 defines useful or effective condensing area as total condensing area
minus the area used for desuperheating and the area used for subcooling.
Equation 1-
Useful or effective condensing area = (Total condenser area) - (Condenser area used for
desuperheating and subcooling)
**ASHRAE Fundamentals Handbook, Chapter 16, Tables 9
& 10.
As one can see, the more desuperheating and liquid
subcooling that is done by the condenser, the less useful condenser area there will be.
This will raise condensing pressures and compression ratios and cause inefficiencies with
higher power draws.
A more efficient way to subcool liquid can be to increase
the pressure of the liquid without raising the temperature. This will put the liquid at a
higher pressure, thus it will have a higher associated saturation temperature, but will
not change its actual temperature. This liquid is subcooled in an amount equal to the
difference between the saturation temperature and the actual temperature. You now have
liquid below its saturation temperature for that new pressure. By increasing the pressure
of the subcooled liquid to overcome any pressure losses that occur in the liquid line,
condensing pressures can be allowed to fall to their lowest pressures attainable. Another
term for attaining the lowest possible head pressure is called floating the head pressure.
Condensing temperatures of -6.66oC (20oF) are not uncommon in low
temperature systems incorporating liquid pressure amplification.
However, if one tries to float the head pressure with the
ambient, these lower head pressures will require more subcooling for the same pressure
drops in the liquid line to prevent flashing. This phenomenon happens because the pressure
vs. temperature graph of refrigerants is non-linear. The graph of pressure vs. temperature
is much flatter at the lower pressures, meaning that the same amount of liquid subcooling
is needed to overcome less of a pressure drop at these lower pressures and temperatures
Fig 4.
Figure 4
Non-linear pressure vs. temperature curves of a halocarbon
refrigerant.
This is one of the reasons why liquid refrigerant pumping
is incorporated in the system when the head pressure is floated with the ambient. It
subcools the liquid by increasing the pressure of the liquid and forces the liquid to have
a new higher saturation temperature. Thus, flash gas is prevented when head pressures are
allowed to float because liquid refrigerant pumping insures that the liquid line pressure
(and saturation temperature) are always higher than the actual liquid temperature.
Also, as head pressure is reduced without liquid
refrigerant pumping and the liquid experiences the same pressure drop through the liquid
line as it did at the higher condensing pressures, the flash gas will now occupy more
volume in the liquid line because of the higher specific volume of the flashed vapors. The
thermostatic expansion valve will begin to hunt, starve the evaporator, and system
capacity will be reduced. Consider the curve for a hydro chlorofluorocarbon (HCFC)
refrigerant Fig. 5.
Figure 5
Temperature vs. percent Weight vs. percent Volume of a hydrochlorofluoocarbon (HCFC)
refrigerant.
As the pressure in the liquid line drops, progressively
more liquid will flash into vapor to cool the remaining liquid to the saturation
temperature corresponding to the progressively lower pressure. With an 55.15 kPa (8 psi)
pressure drop, the flash gas, by weight, will be 2% with a 37.77oC (100oF)
condensing temperature. The vapor bubbles in the liquid line are now very compressed and
occupy only 20% of the volume in the liquid line.
However, reduce the condensing temperature to 10.0oC
(50oF) and the flashing vapor will occupy 38% of the liquid line volume. This
vapor reduces the flow through the expansion valve, has little refrigeration effect, and
must be recompressed after doing work. Again, system capacity will suffer, the evaporator
will starve, and the thermostatic expansion valve will begin to hunt. This is the primary
value of the liquid refrigerant pumping system - to insure solid liquid to the
thermostatic expansion valve, so the valve can supply adequate liquid to the evaporator.
In the past, designers of air conditioning and refrigeration systems picked an outdoor
design condition for the system. This outdoor design condition typically was a temperature
that will not be reached any more than 2% of the time in the system's life.
This design condition also occurs only a couple of hour at
a time when reached. The selection of the condenser is usually made, however, based on
this seldom reached condition.
Some years ago, when energy was much cheaper, designers
would select condensing temperatures at 11.1oC to 16.6oC (20oF
to 30oF) above the ambient. This was done because it was thought the higher
condensing temperatures and pressures would enhance the flow through the metering device
to outweigh any inefficiencies from the high compression ratios. This would force
condensing temperatures and pressures higher, causing high compression ratios and lower
efficiencies. With today's escalating energy costs, designers are specifying larger
condensers with condensing temperatures 5.5oC to 8.3oC (10oF
to 15oF) above the ambient. The significant energy savings from lower
compression ratios and possibly increased subcooling of liquid negate the higher costs of
the larger condenser.
After much research with metering valve suppliers, it was
found out that thermostatic expansion valves would work with much less pressure drop
across them than expected in the past, as long as pure liquid was supplied to them. The
balanced port TEV design today is noted for its low pressure drop performance. With this
new knowledge, condensing pressures and temperatures were allowed to float downward with
the ambient temperature. In fact, a majority of the outdoor temperatures in the USA are
below 21.1oC
(70oF) more of the time than they are above.
Liquid pumping allows the systems to take advantage of lower ambient temperatures rather
than force the condensing temperatures higher. The compressor capacity increases about 6%
for every 5.5oC (10oF) drop in condensing temperature***. However,
pressure drops across the expansion valve of less than 206.8kPa (30 psi) should be avoided
for proper control of feeding of liquid to the evaporator. For an evaporator to operate at
peak efficiency, it must operate with as high a percent of liquid to vapor ratio as
possible entering the evaporator.
***ASHRAE Fundamentals Handbook, Chapter 16, Tables
9 - 10. |